The Reason That Conerete Mixer Not Dischage After Mixing Time
Writer:Admin Time:16/09/12Some customer will encounter this kind of phenomenon, in the process of automatic production, after smooth concrete batching plant mixing time goes to zero, mixer discharge.
This is because the concrete mixer weighing instrument displays the weight of data from the sensor junction box sent over the current signal, the instrument shows the weight fluctuation, then the sensor junction box transmission over the current fluctuations. Sensor internal bridge damage or sensor junction box wiring head loose will cause current fluctuations.
With many years of batch plants concrete production manufacturer to tell you that there are three kinds of processing methods:
1. Check if the pause button on the console is pressed or reset if pressed. In this case,
2, check the computer monitor interface on the prohibition of the discharge control is activated, such as activation is canceled.
3, check the discharge solenoid valve is working properly.